Https amzn to 2x8noge usa made refrigeration ratchet.
Refrigeration king valve positions.
In the video andrew describes the following positions.
The front seat position can be used to isolate refrigeration system.
Full size ports for unrestricted flow non directional.
The gauge port is closed and the valve is open allowing refrigerant to flow through the system.
The valve is front seated when the stem is turned all the way in clockwise.
My paperback ebook.
This catalog provides product data sheets of herl valves and components operating instructions how to order information and contact addresses.
If the valve stem is all the way in the valve is considered to be in the front seated.
When referring to the king valve most air conditioning technicians are referring to the valve which is found downstream from a liquid line receiver.
Back seated all the way out fully counter clockwise this position provides full operational flow through the valve body but is closed to the access port.
Valve may be installed in any position full refrigeration service temperature range of 40 f to 325 f valves with access fittings also available.
This position is called front seated because the valve is seated on the front port of the valve.
Check out a demo of housecall pro here.
It is also commonly referred to as a liquid.
Additional information in the appendices provide ce declaration of conformity and safety guide.
Front seated position the valve stem is turned fully clockwise to effectively stop the flow of refrigerant vapour from the suction line union on the low pressure side of the compressor and to the discharge line union on the high pressure side of the compressor.
The king valve is unique in its position because it allows you to pump down a system by closing it and running the compressor until all or most refrigerant is pumped out of the low side of the system and into the condenser and receiver.
In this position the line port is closed but the middle port is open to the service port figure 25 10.
These types of valves have no schrader port so there will be no pressure on the port when the valve stem is back seated.